picv - cocon qFC pn16
Application:
The pressure independent control valve “Cocon QFC” is designed
to be installed in heating and cooling systems with closed water
circuit (e.g. central heating systems, surface heating systems, fan
coil units, chilled ceilings and fan convectors) for automatic flow
control (hydronic balancing). It can also be used for room
temperature control by modifying the flow rate with the help of
actuators.
Technical data:
Max. operating temperature: 120 °C
Min. operating temperature: -10 °C
Max. operating pressure: 16 bar (1600 kPa) 25 bar (2500 kPa)
Max. differential pressure: 4 bar (400 kPa)
Fluid: Water or mixtures of water and ethylene/propylene glycol (max. 50 %)
ph value 6.5-10
Max. Closing pressure
in flow direction: 16 bar (1600 kPa)
25 bar (2500 kPa) 1146649-56